D-500 MK3 User Manual Firmware V-14.2
- 206 -
The unit offers the possibility of SNMP communication through its Ethernet port (100Mb)
Below parameters may be set to the
controller:
Control Buttons
Remote Controlled Digital Outputs
Below parameters may be read from the
controller:
Mains voltages (L1, L2, L3, L12, L23, L31)
Mains Currents (I1, I2, I3, IN)
Mains Active Power (L1, L2, L3, Total)
Mains Reactive Power (L1, L2, L3, Total)
Mains Apparent Power (L1, L2, L3, Total)
Mains Power Factor (L1, L2, L3, Total)
Mains Phase Angle
Mains Frequency
Genset voltages (L1, L2, L3, L12, L23, L31)
Genset Currents (I1, I2, I3, IN)
Genset Active Power (L1, L2, L3, Total)
Genset Reactive Power (L1, L2, L3, Total)
Genset Apparent Power (L1, L2, L3, Total)
Genset Power Factor (L1, L2, L3, Total)
Genset Phase Angle
Genset Frequency
Genset Operation Mode
Genset Operation Status
Charge Input Voltage
Battery Voltage
Oil Pressure
Coolant Temperature
Fuel Level
Oil Temperature
Canopy Temperature
Ambient Temperature
Engine RPM
Total Genset Cranks Counter
Total Genset Runs Counter
Engine Run Hours Counter
Total kW-h counter
Total kVAR-h (inductive) Counter
Total kVAR-h (capacitive) Counter
Engine Hours to Service-1 Counter
Days to Service-1 Counter
Engine Hours to Service-2 Counter
Days to Service-2 Counter
Engine Hours to Service-3 Counter
Days to Service-3 Counter
Shutdown Alarm List
Loaddump Alarm List
Warning Alarm List
Remote Controlled Digital Outputs
The supported version of the SNMP is V1.0 and V1.1
The SNMP MIB file is available at DATAKOM technical support.
38. SNMP COMMUNICATIONS

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Datakom D-500 MK3 and is the answer not in the manual?

Datakom D-500 MK3 Specifications

General IconGeneral
Magnetic Pickup Voltage0.5 to 50 V AC
Maximum Humidity95% non-condensing
Humidity95% RH (non-condensing)
Communication PortsRS-485
DisplayLCD with backlight
Enclosure MaterialPlastic (ABS)

Related product manuals