D-500L Firmware V-5.8
K35D03-EN - 88 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Charge Voltage Fail
Timer
sec
0
120
1
If the charge alternator voltage goes
under limits during this timer, a charge
alternator voltage fault will occur.
Engine Heating
Temperature
°C
0
80
0
If it is requested that the engine runs
without load until reaching a certain
temperature, this parameter defines the
temperature.
Engine Start Delay
min
0
720
1
This is the time between the mains fails
and the fuel solenoid turns on before
starting the genset. It prevents
unwanted genset operation in battery
backed-up loads.
Preheat Timer
sec
0
30
0
This is the time after the fuel solenoid is
energized and before the genset is
started. During this period the
PREHEAT relay output is energized (if
assigned by Relay Definitions)
Crank Timer
sec
1
15
6
This is the maximum start period.
Starting will be automatically cancelled
if the genset fires before the timer.
Wait Between Starts
sec
1
240
10
This is the waiting period between two
start attempts.
Engine Heating Timer
sec
0
240
4
This is the period used for engine
heating before load transfer.
Engine Heating Method
-
0
1
0
The genset will not take the load before
engine heating is completed.
0: engine is heated during Engine
Heating Timer.
1: engine is heated until the coolant
temperature reaches the Engine
Heating Temperature and at least
during the Engine Heating Timer.
Cooldown Timer
sec
0
600
120
This is the period that the generator runs
for cooling purpose after the load is
transferred to mains.
Stop Solenoid Timer
sec
0
90
10
This is the maximum time duration for
the engine to stop. During this period
the STOP relay output is energized (if
assigned by Relay Definitions). If the
genset has not stopped after this
period, a FAIL TO STOP warning
occurs.
Number of Starts
-
1
6
3
Number of Starts
Choke Timer
sec
0
240
5
This is the control delay of CHOKE
output.
The choke output is activated together
with the crank output. It is released
after this delay or when engine runs
(whichever occurs first).
16.3. ENGINE PARAMETERS GROUP (continued)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Datakom D Series and is the answer not in the manual?

Datakom D Series Specifications

General IconGeneral
BrandDatakom
ModelD Series
CategoryController
LanguageEnglish

Related product manuals