D-500L Firmware V-5.8
K35D03-EN - 46 -
DC Supply Range: 9.0 to 33.0 V-DC.
DC power consumption:
250 mA-DC typical @12V-DC
125 mA-DC typical @24V-DC
500 mA-DC max. @12V-DC
250 mA-DC max. @24V-DC
Alternator voltage: 0 to 330 V-AC (Ph-N), 0 to 570V Ph-Ph
Alternator frequency: 0-500 Hz.
Mains voltage: 0 to 330 V-AC (Ph-N) , 0 to 570V Ph-Ph
Mains frequency: 0-500 Hz.
Current Inputs: from current transformers. ../5A.
CT Range: 5/5A to 5000/5A
VT Range: 0.1/1 to 6500 / 1
kW Range: 0.1kW to 65000 kW
Accuracy:
Voltage: 0.5%+1digit
Current: 0.5%+1 digit
Frequency: 0.5%+1 digit
Power(kW,kVAr): 1.0%+2digit
Power factor: 0.5 %+1digit
Digital inputs: input voltage 0 to 36 V-DC.
Analog input range: 0-5000 ohms.
Mains and genset contactor outputs: 16Amps@250V
DC Outputs: Relay outputs, positive switching NO contacts. 10Amps@28V-DC
Cranking dropouts: survives 0V for 100ms.
Magnetic pickup voltage: 0.5 to 30V-RMS.
Magnetic pickup frequency: 10 to 10000 Hz.
Charge Alternator Excitation: 100mA @12VDC, 200mA @24VDC
USB Device: USB 2.0 Full speed
USB Host: USB 2.0 Full speed
RS-485 Port: selectable baud rate
RS-232 Port: selectable baud rate
Operating temperature: -20°C to 70°C (-4 to +158 °F).
Storage temperature: -40°C to 80°C (-40 to +176°F).
Maximum humidity: 95% non-condensing.
IP Protection: IP54 from front panel, IP30 from the rear.
Dimensions: 200 x 148 x 46mm (WxHxD)
Panel Cut-out Dimensions: 176 x 121 mm minimum.
Weight: 450 g (approx.)
Case Material: High Temperature, non-flammable, ROHS compliant ABS/PC
Mounting: Flush mounted with rear retaining plastic brackets.
EU Directives Conformity
-2006/95/EC (low voltage)
-2004/108/EC (electro-magnetic compatibility)
Norms of reference:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
UL Compatibility: UL 6200, Controls for Stationary Engine Driven Assemblies (Certificate Number -
20140725-E314374)
CSA Compatibility: CAN/CSA C22.2 No. 14-2005 – Industrial Control Equipment
8. TECHNICAL SPECIFICATIONS