D-500L Firmware V-5.8
K35D03-EN - 43 -
The positive terminal of the DC Supply.
Power supply negative connection.
Protected
Semiconductor
Outputs
This relay has programmable function,
selectable from a list. Factory set as
CRANK output.
This relay has programmable function,
selectable from a list. Factory set as FUEL
output.
This relay has programmable function,
selectable from a list. Factory set as
ALARM output.
This relay has programmable function,
selectable from a list. Factory set as
PREHEAT output.
Connect the charge alternator’s D+
terminal to this terminal. This terminal will
supply the excitation current and measure
the voltage of the charge alternator.
Resistor measuring
input,
Connect to the oil pressure sender.
Do not connect the sender to other
devices.
Connect to the coolant temperature
sender. Do not connect the sender to
other devices.
Connect to the fuel level sender.
Do not connect the sender to other
devices.
Ground potential for analog senders.
Connect to the engine body, close to
senders.
The input has programmable function.
Factory set as LOW OIL PRESSURE
SWITCH.
The input has programmable function.
Factory set as HIGH TEMP SWITCH.
The input has programmable function.
Factory set as EMERGENCY STOP.
The input has programmable function.
Factory set as SPARE INPUT-1.
The input has programmable function.
Factory set as SPARE INPUT-2.
The input has programmable function.
Factory set as SPARE INPUT-3.
The input has programmable function.
Factory set as FORCE OFF MODE.
AC signal driving
output and detector
input
This input is specially designed for LOW
COOLANT LEVEL detection. The terminal
is driven with a low amplitude pure sinus
waveform. It does not cause waer of the
detector electrode.