D-500L Firmware V-5.8
K35D03-EN - 23 -
Structure:
Relay output, normally closed contact. One terminal is internally
connected to mains phase L1 input.
Max switching current:
16A @250VAC
Max switching voltage:
440VAC
Max switching power:
3000VA
Structure:
Relay output, normally open contact. One terminal is internally
connected to genset phase L1 input.
Max switching current:
16A @250VAC
Max switching voltage:
440VAC
Max switching power:
4000VA
Structure:
Positive relay output, NO contact
Function
programmable function, selectable from list.
Max continuous current:
10.0 ADC
Max switching voltage:
33 VDC
3.9. GENERATOR CONTACTOR OUTPUT
3.10. DIGITAL OUTPUTS
3.8. MAINS CONTACTOR OUTPUT