Status text Condition Comment
MPE ACTIVE
Genset running in mains power export
mode.
DG BLOCKED FOR START
Generator stopped and active alarm(s) on
the generator.
GB ON BLOCKED
Generator running, GB open and an
active Trip GB alarm.
SHUTDOWN OVERRIDE The configurable input is active.
ACCESS LOCK
The configurable input is activated, and
the operator tries to activate one of the
blocked keys.
GB TRIP EXTERNALLY
Some external equipment has tripped the
breaker.
An external trip is logged in the event log.
MB TRIP EXTERNALLY
Some external equipment has tripped the
breaker.
An external trip is logged in the event log.
IDLE RUN
The Idle run function is active. The genset
will not stop until a timer has expired.
IDLE RUN ###.#min
The Idle run function is active and the
timer is counting down.
COMPENSATION FREQ Compensation is active.
The frequency is not at the nominal
setting.
Aux. test ##.#V ####s
Battery test activated, and the timer is
counting down.
DELOAD
Decreasing the load of the genset in order
to open the breaker.
START DG(s) IN ###s The start genset set point is exceeded. Genset will start when timer expires.
STOP DG(s) IN ###s The stop genset set point is exceeded. Genset will stop when timer expires.
START PREPARE The start prepare relay is activated.
START RELAY ON The start relay is activated.
START RELAY OFF
The start relay is deactivated during the
start sequence.
MAINS FAILURE
Mains failure and mains failure timer
expired.
MAINS FAILURE IN ###s
Frequency or voltage measurement is
outside the limits.
The timer shown is the mains failure
delay.
MAINS U OK DEL ####s Mains voltage is OK after a mains failure. The timer shown is the mains OK delay.
MAINS f OK DEL ####s
Mains frequency is OK after a mains
failure.
The timer shown is the mains OK delay.
Hz/V OK IN ###s
The voltage and frequency on the genset
is OK.
When the timer runs out, it is allowed to
operate the generator breaker.
COOLING DOWN ###s Cooling-down period is activated.
GENSET STOPPING
This info is shown when cooling down has
finished.
EXT. STOP TIME ###s
---xx-------- >00< ------------ Generator is synchronising.
The "xx" marks the actual generator
phase angle position in the
synchronisation. When the "xx" is aligned
OPERATOR's MANUAL 4189341186E EN Page 17 of 38