Status text Condition Comment
over the 00 centre, the generator is
synchronised.
TOO SLOW 00<-------------
Generator running too slow during
synchronisation.
-----------> 00 TOO FAST
Generator running too fast during
synchronisation.
EXT. START ORDER A planned AMF sequence is activated.
There is no failure on the mains during
this sequence.
SELECT GENSET MODE
Power management has been deactivated
and no other genset mode has been
selected.
RAMP TO #####kW
The power ramp is ramping in steps, and
the next step that will be reached after the
timer has expired will be displayed.
DERATED TO #####kW Displays the ramp-down set point.
UNEXPECTED GB ON BB
Another generator breaker is closed on to
the busbar (due to a GB position failure)
while no voltage is present on the busbar.
This indicates that other breakers cannot
close to the busbar because of position
failure on one or more GBs.
WARM UP RAMP Warm up ramp is active.
The available power is limited until the
predefined temperature is reached or
when the input which activated warm up
ramp is set low.
SUNSPEC IDENTIFYING* Connecting to PV inverter. Only Sunspec inverters
SUNSPEC INCOMPATIBLE* PV inverter is not compatible. Only Sunspec inverters
SUNSPEC INITIALIZED* PV inverter is successfully initialized. Only Sunspec inverters
NOTE *Only AGC 150 Hybrid version.
4.4 Texts only related to power management
Table 4.1 All controller types
Status text Condition Comment
BROADCASTING APPL. #
Broadcast of an application through the
CAN line.
Broadcasts one of the four applications
from one AGC 150 to the other controllers
in the power management system.
RECEIVING APPL. # Receiving an application.
BROADCAST COMPLETED Successful broadcast of an application.
RECEIVE COMPLETED Application received successfully.
BROADCAST ABORTED Broadcast terminated.
RECEIVE ERROR Application is not received correctly.
QUICK SETUP ERROR Quick setup of the application failed.
MOUNT CAN CONNECTOR
Connect the power management CAN
line.
ADAPT IN PROGRESS
The AGC 150 is receiving the
application,to which it has just been
connected.
OPERATOR's MANUAL 4189341186E EN Page 18 of 38