No. Name Function
13 Breaker symbols
Green: Breaker is ON.
Green flashing: Synchronising or de-loading.
Red: Breaker failure.
14 Generator
Green: Generator voltage and frequency are OK. The controller can synchronise and close the
breaker.
Green flashing: The generator voltage and frequency are OK, but the V&Hz OK timer is still running.
The controller cannot close the breaker.
Red: The generator voltage is too low to measure.
15
Engine
Green: There is running feedback.
Green flashing: The engine is getting ready.
Red: The engine is not running, or there is no running feedback.
16 Stop Stops the genset if SEMI-AUTO or Manual is selected.
17 Start Starts the genset if SEMI-AUTO or Manual is selected.
18 Load symbol
OFF: Power management application.
Green: The supply voltage and frequency are OK.
Red: Supply voltage/frequency failure.
2.1.2 Display settings
It is possible to adjust the settings for the display to compensate for ambient lighting. Configure these settings under Settings >
Basic settings > Controller settings > Display > Display control.
Parameter no.
Text Range Default
9151 Backlight dimmer 0 to 15 12
9152 Green LEDs dimmer 1 to 15 15
9153 Red LEDs dimmer 1 to 15 15
9154 Contrast level -20 to +20 0
9155 Sleep mode timer 1 to 1800 s 60 s
9156 Enable (Sleep mode timer)
OFF
ON
ON
9157 Alarm Jump
OFF
ON
ON
9158 Engineering units
Bar/Celcius
PSI/Fahrenheit
Bar/Celcius
OPERATOR's MANUAL 4189341186E EN Page 6 of 38