2. Controller overview
2.1 Overview of buttons and LEDs
2.1.1 Front overview
4
3
3
5
6
7
8
9
15 14 11 1112 12
1
17
16
2 3 3
18
1013
No. Name Function
1 Power ON
Green: The controller power is ON.
OFF: The controller power is OFF.
2 Display screen
Resolution: 240 x 128 px.
Viewing area: 88.50 x 51.40 mm.
Six lines, each with 25 characters.
3 Navigation Move the selector up, down, left and right on the screen.
4 OK
Enter the Menu system.
Confirm the selection on the screen.
5 Back Go to the previous page.
6 AUTO mode
The controller automatically starts and stops gensets according to the system settings. No operator
actions are needed.
7 Silence horn Turns off an alarm horn (if configured) and enters the Alarm menu.
8 Shortcut menu Gives access to: Jump menu, Mode selection, Test, Lamp test, Hybrid (PV semi start and stop).
9
SEMI-AUTO
mode
The controller cannot automatically start, stop, connect or disconnect the genset.
The operator can start, stop, connect or disconnect the genset.
The controller automatically synchronises before closing a breaker, and automatically de-loads before
opening a breaker.
10 Mains symbol
Green: Mains voltage and frequency are OK. The controller can synchronise and close the breaker.
Red: Mains failure.
11 Close breaker Press to close the breaker.
12 Open breaker Press to open the breaker.
OPERATOR's MANUAL 4189341186E EN Page 5 of 38