Access the Alarm list with the Utility Software
To open the Alarm list with the Utility Software, press the Alarms button.
CAUTION
If an alarm is blocking a genset in AUTO mode from starting, the genset will automatically start and close the breaker if the
condition that triggered the alarm has disappeared and the alarm has been acknowledged.
5.2 Logs menu
The log shows three menus:
1. Event log: Shows up to 500 events, for example: Auto Mains Failure.
2. Alarm log: Shows up to 500 alarms, for example: Emergency STOP. Only the latest 100 alarms are shown on the display unit,
while the remaining alarms is shown in the Utility Software.
3. Battery test log: Shows up to 52 tests, either Test OK or Test failed.
Access the Log menu from the display unit
1. From the View menu, press the button.
2. Scroll to Logs with the and buttons.
Settings
Service View
Alarm list
3. Press the button to select Logs.
4. Choose the preferred Log list.
5. Press the button to select the preferred Log list.
6. Press the button to leave the Log list.
Access the Log list with the Utility Software
Open the Log menu with the Utility Software:
1. In the left menu, press the Logs button.
2. In the task bar, press the Read logs
button.
3. Choose the preferred Log list.