4.3 Status line texts
Status text Condition Comment
BLOCK Block mode is activated.
SIMPLE TEST
Test mode is activated.
LOAD TEST
FULL TEST
SIMPLE TEST ###.#min
Test mode is activated and test timer
counting down.
LOAD TEST ###.#min
FULL TEST ###.#min
ISLAND MAN
Genset stopped or running and no other
action taking place.
ISLAND SEMI
ISLAND AUTO
Genset stopped in AUTO mode.
READY ISLAND AUTO
ISLAND ACTIVE Genset running in AUTO mode.
AMF MAN
Genset stopped or running and no other
action taking place.
AMF SEMI
AMF AUTO
Genset stopped in AUTO mode.
READY AMF AUTO
Genset is stopped, ready to auto start with
mains failure.
AMF ACTIVE Genset running in AUTO mode.
FIXED POWER MAN
Genset stopped or running and no other
action taking place.
FIXED POWER SEMI
READY FIXED P AUTO Genset stopped in AUTO mode.
FIXED POWER ACTIVE Genset running in AUTO mode.
PEAK SHAVING MAN
Genset stopped or running and no other
action taking place.
PEAK SHAVING SEMI
PEAK SHAVING AUTO
READY PEAK SHAV AUTO Genset stopped in AUTO mode.
PEAK SHAVING ACTIVE Genset running in AUTO mode.
LOAD TAKE OVER MAN
Genset stopped or running and no other
action taking place.
LOAD TAKE OVER SEMI
LOAD TAKE OVER AUTO
READY LTO AUTO Genset stopped in AUTO mode.
Genset is stopped, ready to start and load
take-over.
LTO ACTIVE Genset running in AUTO mode.
Genset is running, ready for load take-
over.
MAINS P EXPORT MAN
Genset stopped or running and no other
action taking place.
MAINS P EXPORT SEMI
MAINS P EXPORT AUTO
READY MPE AUTO Genset stopped in AUTO mode.