Status text Condition Comment
SETUP IN PROGRESS
The new controller is being added to the
existing application.
SETUP COMPLETED
Successful update of the application in all
AGC 150 controllers.
REMOVE CAN CONNECTOR
Remove the power management CAN
lines.
Table 4.2 DG controller
Status text Condition Comment
BLACKOUT ENABLE
This info is shown if a CAN failure is
present in a power management
application.
UNIT STANDBY
If redundant mains units are present, this
message is shown on the redundant unit.
DELOADING BTB XX
DG units are load sharing asymmetrically
to de-load BTB XX dividing two sections in
an island application.
BTB XX DIVIDING SEC.
BTB XX is dividing two sections in an
island application.
SYNCHRONISING TB XX TB XX is synchronising.
SYNCHRONISING MB XX MB XX is synchronising.
SYNCHRONISING BTB XX BTB XX is synchronising.
De-loading TB XX
Displays that a tie breaker is being de-
loaded in SEMI-AUTO mode.
Table 4.3 Mains controller
Status text Condition Comment
UNIT STANDBY
If redundant mains units are present this
message is shown on the redundant unit.
TB TRIP EXTERNALLY
Some external equipment has tripped the
breaker.
An external trip is logged in the event log.
Table 4.4 BTB controller
Status text Condition Comment
DIVIDING SECTION
A BTB unit is dividing two sections in an
island application.
READY AUTO OPERATION
BTB unit in AUTO mode and ready for
breaker operation (no active BTB trip
alarm).
SEMI OPERATION BTB unit in SEMI-AUTO mode.
AUTO OPERATION
BTB unit in AUTO mode, but not ready for
breaker operation (active BTB trip alarm).
BLOCKED FOR CLOSING Last open BTB in a ring bus.
BTB TRIP EXTERNALLY
Some external equipment has tripped the
breaker.
An external trip is logged in the event log.