Figure 4 Installing a power supply unit
Verifying successful power supply replacement from the ACM
After a power supply is replaced, you can run the FRU command line verification from the ACM to
ensure that the replacement was successful.
Procedure
1. From the ACM, type the following command: # showfru power
The screen displays that the system is collecting data. When the data collection is
completed, a screen similar to the following displays status information for the power
supplies.
acme-dp4400-ACM:~ # showfru power
Collecting Data............
_________________________________________________________________
| ID| Status| Redundancy| Model | FW Version|
|================================================================|
| 1 | OK | Full | PWR SPLY,1100W,RDNT,ARTESYN| 00.1B.53 | *
| 2 | OK | Full | PWR SPLY,1100W,RDNT,ARTESYN| 00.1B.53 |
2. Verify that the status for both power supplies is "OK".
Hard drive replacement overview
Hard drives
Hard drives are supplied in hot swappable hard drive carriers that fit in the hard drive slots. You do
not need to shut down the system to replace a hard drive.
CAUTION
Before attempting to remove or install a hard drive while the system is running, see
the documentation for the storage controller card to ensure that the host adapter is
configured correctly.
CAUTION Do not turn off or restart your system while a hard drive is being formatted. Doing
so can cause a hard drive failure.
Remove and replace assemblies
18 Dell EMC Integrated Data Protection Appliance DP4400 Service Procedures