a Partially tighten the rst screw (approximately three turns).
b Tighten the second screw completely.
c Return to the rst screw and tighten it completely.
If the PHM slips o the blue retention clips when the screws are partially tightened, follow these steps to secure the PHM:
a Loosen both the heat sink screws completely.
b Lower the PHM on to the blue retention clips, following the procedure described in step 2.
c Secure the PHM to the system board, following the replacement instructions listed in step 3 above.
NOTE: The processor and heat sink module retention screws should not be tightened to more than 0.11 kgf-m (1.13 N.m
or 10+/-0.2 in-lbf).
Figure 57. Installing a processor and heat sink module
Next steps
1 Install the air shroud.
2 Follow the procedure listed in After working inside your sled.
iDRAC card
In the PowerEdge MX740c, iDRAC is not embedded on the system board. The iDRAC is a separate card unlike other 14G PowerEdge
servers. The vFlash card for the PowerEdge MX740c is available on the iDRAC card.
Removing the iDRAC card
Prerequisites
1 Follow the safety guidelines listed in Safety Instructions.
2 Follow the procedure listed in Before working inside the sled.
3 Remove the air shroud.
Installing and removing system components
85