Supported operating systems
The PowerEdge T640 system supports the following operating systems:
• Canonical Ubuntu LTS
• Citrix XenServer
• Microsoft Windows Server with Hyper-V
• Red Hat Enterprise Linux
• SUSE Linux Enterprise Server
• VMware ESXi
For more information on the specic versions and additions, see https://www.dell.com/support/home/Drivers/SupportedOS/poweredge-
t640.
Cooling fan specications
The cooling fans are integrated into the system to dissipate the heat generated by the functioning of the system. These fans provide
cooling for the processors, expansion cards, and memory modules.
Your system supports a total of eight fans, including six hot-swappable fans and two external fans. Two hot-swappable fans are mounted in
rear side of the air shroud. The other four hot-swappable (middle) fans are mounted in the fan assembly that is located in the chassis
between the hard drive bay and the processors. The two external fans are mounted on the outside of the chassis for GPU congurations.
There are two additional fans integrated in the power supplies to cool the power supplies and provide additional cooling for the whole
system.
The below listed congurations, features, and the PCIe expansion cards are supported only with the four hot-swappable (middle) fans
installed:
• Fan redundancy
• Fresh air condition
• NVMe/PCIe SSD
• 3.5 inch x 18 hard drives chassis
• Mellanox CX4 DP 100 Gb QSFP NIC (0272F)
• Mellanox CX4 DP 100 Gb NIC (068F2)
• Mellanox CX4 SP 100 Gb NIC (6W1HY)
• Mellanox DP 40 Gb QSFP NIC (C8Y42)
• Intel QP 10 Gb Base-T NIC (K5V44)
• Solarare Sunspot DP 10Gb NIC (NPHCM)
• Solarare Nova DP 10Gb NIC (WY7T5)
• Qlogic DP 10Gb V1 NIC (VCXN5)
Listed below are the restrictions for fan redundancy:
• GPGPU congurations are not supported at 35deg. C of ambient or above.
• Mellanox 100G NICs are not supported.
For information on the restriction for fresh air condition, see the Expanded operating temperature restrictions topic in the Technical
Specication section.
PSU specications
The Dell EMC PowerEdge T640 system supports up to two AC or DC redundant power supply units (PSUs).
Technical