Table 16. Temperature specications
Temperature Specications
Storage –40°C to 65°C (–40°F to 149°F)
Continuous operation (for altitude less than 950 m or 3117
ft)
10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment.
Fresh air For information about fresh air, see Expanded Operating Temperature
section.
Maximum temperature gradient (operating and storage) 20°C/h (68°F/h)
Table 17. Relative humidity specications
Relative humidity Specications
Storage 5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be
non-condensing at all times.
Operating 10% to 80% relative humidity with 29°C (84.2°F) maximum dew point.
Table 18. Maximum vibration specications
Maximum vibration Specications
Operating 0.26 G
rms
at 5 Hz to 350 Hz (all operation orientations).
Storage 1.88 G
rms
at 10 Hz to 500 Hz for 15 min (all six sides tested).
Table 19. Maximum shock specications
Maximum vibration Specications
Operating Six consecutively executed shock pulses in the positive and negative x, y,
and z axes
Storage Six consecutively executed shock pulses in the positive and negative x, y,
and z axes (one pulse on each side of the system) of 71 G for up to 2 ms.
Table 20. Maximum altitude specications
Maximum altitude Specications
Operating
3048 m (10,000 ft)
Storage 12,000 m (39,370 ft)
Table 21. Operating temperature de-rating specications
Operating temperature de-rating Specications
Up to 35°C (95°F) Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m
(3,117 ft).
35°C to 40°C (95°F to 104°F) Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950 m
(3,117 ft).