Chapter 6 Control Mode of Operation ASDA-M
6-22 Revision December, 2014
P1-25
VSF1
Low-frequency Vibration Suppression
(1)
Address: 0132H
0133H
Parameter
Attribute
Parameter for individual axis
Related Section:
Section 6.2.9
Operational
Interface
Panel / Software Communication
Default
1000
Control
Mode
PT / PR
Unit
0.1 Hz
Range
10 ~ 1000
Data Size
16bit
Format
DEC
Example
150= 15 Hz
Settings
The setting value of the first low-frequency vibration suppression.
If P1-26 is set to 0, then it will disable the first low-frequency filter.
P1-26
VSG1
Low-frequency Vibration Suppression
Gain (1)
Address: 0134H
0135H
Parameter
Attribute
Parameter for individual axis
Related Section:
Section 6.2.9
Operational
Interface
Panel / Software Communication
Default
0
Control
Mode
PT / PR
Unit
-
Range
0 ~ 9 (0: Disable the first low-frequency
filter)
Data Size
16bit
Format
DEC
Settings
The first low-frequency vibration suppression gain. The bigger the
value it is, the better the position response will be. However, if the
value is set too big, the motor will not be able to operate smoothly.
It is suggested to set the value to 1.

Table of Contents

Other manuals for Delta ASDA-M Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ASDA-M Series and is the answer not in the manual?

Delta ASDA-M Series Specifications

General IconGeneral
BrandDelta
ModelASDA-M Series
CategoryServo Drives
LanguageEnglish

Related product manuals