ASDA-M Chapter 6 Control Mode of Operation
Revision December, 2014 6-23
P1-27
VSF2
Low-frequency Vibration Suppression
(2)
Address: 0136H
0137H
Parameter
Attribute
Parameter for individual axis
Related Section:
Section 6.2.9
Operational
Interface
Panel / Software Communication
Default
1000
Control
Mode
PT / PR
Unit
0.1 Hz
Range
10 ~ 1000
Data Size
16bit
Format
DEC
Example
150 = 15 Hz
Settings
The setting value of the second low-frequency vibration
suppression. If P1-28 is set to 0, then it will disable the second
low-frequency filter.
P1-28
VSG2
Low-frequency Vibration Suppression
Gain (2)
Address: 0138H
0139H
Parameter
Attribute
Parameter for individual axis
Related Section:
Section 6.2.9
Operational
Interface
Panel / Software Communication
Default
0
Control
Mode
PT / PR
Unit
-
Range
0 ~ 9 (0: Disable the second
low-frequency filter)
Data Size
16bit
Format
DEC
Settings
The second low-frequency vibration suppression gain. The bigger
the value it is, the better the position response will be. However, if
the value is set too big, the motor will not be able to operate
smoothly. It is suggested to set the value to 1.

Table of Contents

Other manuals for Delta ASDA-M Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ASDA-M Series and is the answer not in the manual?

Delta ASDA-M Series Specifications

General IconGeneral
BrandDelta
ModelASDA-M Series
CategoryServo Drives
LanguageEnglish

Related product manuals