ASDA-M Chapter 8 Parameters
Revision December, 2014 8-55
Range
0 ~ 9 (0: Disable the second
low-frequency filter)
Data Size
16bit
Format
DEC
Settings
The second low-frequency vibration suppression gain. The bigger
value it is, the better the position response will be. However, if the
value is set too big, the motor will not be able to smoothly
operate. It is suggested to set the value to 1.
P1-29
AVSM
Auto Low-frequency Vibration
Supression Setting
Address: 013AH
013BH
Parameter
Attribute
Parameter for individual axis
Related Section:
Section 6.2.9
Operational
Interface
Panel / Software Communication
Default
0
Control
Mode
PT / PR
Unit
-
Range
0 ~ 1
Data Size
16bit
Format
DEC
Settings
0: The function is disabled.
1: The value will set back to 0 after vibration suppression.
Description of Auto Mode Setting:
When the parameter is set to 1, it is in auto suppression. When
the vibration frequency is not being detected or the value of
searched frequency is stable, the parameter will set to 0 and save
the low-frequency vibration suppression to P1-25 automatically.
P1-30
VCL Low-frequency Vibration Detection
Address: 013CH
013DH
Parameter
Attribute
Parameter for individual axis
Related Section:
Section 6.2.9
Operational
Interface
Panel / Software Communication
Default
500
Control
Mode
PT / PR