Chapter 2: Specifications and System Configuration
DTM temperature controller operating manual
2-1
Chapter 2
Specifications and System Configuration
2.1 Electrical Specifications
Input power 24V DC
Operating voltage
90% ~ 110% of rated voltage
Power
consumption
Host Max. (maximum number of channels ) 6W + 5W × number of measurement
expansion modules in parallel + 3W × number of I/O expansion module in parallel
Expansion cassette power consumption is already included in the host or
measurement expansion module
Installation
requirement
Please install according to the sequenceHost measurement expansion
modules (Max. 7 modules)I/O expansion modules (Max. 8 modules)If the
measurement expansion modules include DTMN02-x series, be sure to install
DTMN08 / N04 before installing DTMN02-x,
Each DTM group can only expand one DTMN02-x measurement expansion
module
Input sensor
support
Thermocouple : K, J, T, E, N, R, S, B, L, U, TXK, C
RTD: Pt100, JPt100, Ni120, Cu50
Analog input: 0 - 10V, 0 - 5V, 0 - 50mV, 0 - 20mA, 4 - 20mA
Sampling
frequency
0.1 sec./all 8 inputs
Control mode
PID, programmable PID design, ON/OFF, manual
Output types
Relay output, SPST, rated maximum load of AC 250V, 2A resistive load.
Voltage pulse output, DC 12V±10%, rated maximum output current of 20mA.
Analog current output 4~20mA (load impedance must be 500Ω)
Analog voltage output 0~10V (load impedance must be 1,000Ω)
Open drain output, maximum load 30mA/5~24VDC, only for driving SSR.
Input accessory
types
When there is an optional CT device, the customer should select a current
transformer (CT), with selection information as follows:
1. 30A CT model: DT3-CT30A; 2. 100A CT model: DT3-CT100A, resolution of 0.1A
Output functions
(optional)
Optional control output, alarm output, or proportional output (must have an optional
output device type)
Alarm function
(optional)
17 alarm modes may be selected (must have an optional output device type)
Communications
functions
RS-485 communications: support baud rates of 4800/9600/19200/38400/57600/
115200bps
Ethernet communications: supports 10/100Mbps, MDI/MDI-X automatic detection,
1 Port, RJ45
USB communications: supports USB 2.0 Full Speed only for the host