Chapter 4: Output and Alarm Function Configuration
DTM temperature controller operating manual
values
Alarm mode
Alarm output functions
control is implemented, the corresponding alarm will be
generated when in a Stop state.
16
Programmable End action: When the programmable
control is implemented, the corresponding alarm will be
generated when in a End state.
17
CT2 alarm actions: When the CT2 value is lower than the
ALM-L value or is higher than the ALM-
H value, the
corresponding alarm will be generated.
Table – Explanation of alarm mode
4.3.2 Alarm Function Settings
A. ALM action: 17 alarm modes can be available and the mode can be set with writing the
configuring values to the corresponding communications address
B. ALM-H: Set the alarm upper limit in accordance with the alarm mode
C. ALM-H: Set the alarm lower limit in accordance with the alarm mode
D. ALM delay: Setting range: 0~100, units: Seconds
E. ALM option: Turns on/turns off corresponding alarm functions in accordance with Bit0~3,
Bit0~3 = 0 : OFF ; Bit0~3 = 1 : ON
Bit0 = standby;
Bit1 = output reverse;
Bit2 = hold;
Bit3 = peak record (reads peak content as shown in the table below)
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
ALM1 action Hx040 Hx041 Hx042 Hx043 Hx044 Hx045 Hx046 Hx047
ALM1-H Hx088 Hx089 Hx08A Hx08B Hx08C Hx08D Hx08E Hx08F
ALM1-L Hx090 Hx091 Hx092 Hx093 Hx094 Hx095 Hx096 Hx097
ALM1 delay Hx048 Hx049 Hx04A Hx04B Hx04C Hx04D Hx04E Hx04F
ALM1 option Hx050 Hx051 Hx052 Hx053 Hx054 Hx055 Hx056 Hx057
ALM2 action Hx058 Hx059 Hx05A Hx05B Hx05C Hx05D Hx05E Hx05F
ALM2-H Hx098 Hx099 Hx09A Hx09B Hx09C Hx09D Hx09E Hx09F
ALM2-L Hx0A0 Hx0A1 Hx0A2 Hx0A3 Hx0A4 Hx0A5 Hx0A6 Hx0A7
ALM2 delay Hx060 Hx061 Hx062 Hx063 Hx064 Hx065 Hx066 Hx067
ALM2 option Hx068 Hx069 Hx06A Hx06B Hx06C Hx06D Hx06E Hx06F
ALM3 action Hx070 Hx071 Hx072 Hx073 Hx074 Hx075 Hx076 Hx077
ALM3-H Hx0A8 Hx0A9 Hx0AA Hx0AB Hx0AC Hx0AD Hx0AE Hx0AF
ALM3-L Hx0B0 Hx0B1 Hx0B2 Hx0B3 Hx0B4 Hx0B5 Hx0B6 Hx0B7
ALM3 delay Hx078 Hx079 Hx07A Hx07B Hx07C Hx07D Hx07E Hx07F