Chapter 2: Specifications and System Configuration
DTM temperature controller operating manual
2-2
Communication
protocol
RS485: support the Modbus protocol with RTU/ASCII communications format
Ethernet: support Modbus TCP and Ethernet/IP, IEEE802.3, IEEE802.3u
transmission method
USB: support USB2.0 communications standard
Transmission cable
(Ethernet)
Category 5e shielding 100M
Internal connection
functions
Provides internal connection terminals with 24V power and communications signal
provided
Vibration
resistance
10 - 55Hz; 10m/s2; 3-axial directions; 10 min.
Shock resistance
Maximum of 300m/s2; 3-axis, 6-directions; 3 times each
Operating
temperature
0°C - +50°C
Storage
temperature
-20°C - +65°C
Operating altitude
Below 2,000 meters above sea level
Operating humidity
35% to 85% RH (no dew)
Pollution level 2
2.2 Temperature Sensor Type and Temperature Range
Input sensor type
Communication
register value
Temperature
range
Input sensor type
Communication
register value
Temperature
range
Thermocouple K
type
0
-200 -1300°C
Thermocouple TXK
type
10 -150 - 800°C
Thermocouple J
type
1
-100 -1200°C
Platinum resistance
(JPt100)
11 -20 - 400°C
Thermocouple T
type
2
-200 - 400°C
Platinum resistance
(Pt100)
12 -200 - 850°C
Thermocouple E
type
3
0 - 600°C
RTD
sensor (Ni120) 13 -80 - 300°C
Thermocouple N
type
4
-200 -1300°C
R
TD sensor (Cu50) 14 -50 - 150°C
Thermocouple R
type
5
0 - 1700°C
Analog voltage input
(0-5V)
15
-1999 ~ 19999
Thermocouple S
type
6
0
- 1700°C
Analog voltage input
(0-10V)
16
-1999 ~ 19999
Thermocouple B
type
7
100
- 1800°C
Analog current input
(0-20m A)
17
-1999 ~ 19999
Thermocouple L
type
8
-
200 - 850°C
Analog current input
(4-20m A)
18
-1999 ~ 19999
Thermocouple U
type
9
-
200 - 500°C
Analog voltage input
(0-50m V)
19
-1999 ~ 19999
Thermocouple C
type
20
0 -2300°C*
*Note: When the C-type sensor input is switched to Fahrenheit temperature unit, the upper limit of the display
range is 3270°F.