Chapter 2: Specifications and System Configuration
DTM temperature controller operating manual
2-6
2.5 RS485/ USB Communications Protocol Settings
Bit 5 Bit 6 Bit 7
Communication
s protocol
format
OFF OFF OFF
7, E, 1 (default
value)
Bit 1
Communications encoding
ON
OFF
OFF
7,O,1
OFF
ASCII ( default value)
OFF
ON
OFF
7,N,1
ON
RTU
ON
ON
OFF
8,E,1
OFF
OFF
ON
8,O,1
Bit 2 Bit 3 Bit 4
Communicatio
ns rate (bps)
ON OFF ON 8,N,1
OFF OFF OFF
38400 (default
value)
OFF ON ON 7,N,2
ON
OFF
OFF
57600
ON
ON
ON
8,N,2
OFF
ON
OFF
115200
ON ON OFF 19200
Bit 8
Communications address
special code
OFF OFF ON 9600
ON
The communications address is
the switch setting address plus
64
ON OFF ON 4800
OFF
Maintains original set
communications address
(default value)
2.5.1 USB Function
DTMR series host models have a USB communication, which can be connected via DTM soft (software
and operation manual can be downloaded from Delta website). USB connection is only used for parameter
or function setting, because USB has no signal isolation, it cannot be used for long-term monitoring.
Communications protocol
setting switch
Communications protocol setting table
Default settings: All OFF
ASCII 38400,7,E,1