Chapter 2: Specifications and System Configuration
DTM temperature controller operating manual
Example: The following figure illustrates a set of normal operating DTM group station number settings,
DTME08 node no. dial 2 RS485 station number 2 Internal station number 0;
DTMN08 node no. dial 2&A No external communication Internal station number 2 & A; different
from DO & CT expansion module type → station number can be the same
DTM-DOV node no. dial 2 No external communication Internal station number 2; different
from the measurement expansion module & CT expansion module → the station number can be the same
DTM-DOR node no. dial C No external communication Internal station number C;
DTM-CT030 node no. dial 2 No external communication Internal station number 2; different
from the measurement expansion module & DO expansion module → the station number can be the same
And the measurement expansion module 2 sets ≦ 7 sets, the IO expansion module (DO + CT) 3 sets ≦
8 sets, in line with the maximum number of expansion sets of the DTM group