Chapter 2: Specifications and System Configuration
DTM temperature controller operating manual
2.6.3 MODBUS TCP Communication Standards
1. The supported function codes and communication addresses are the same as RS485. Please refer to
the RS485 communication section in Appendix A.
2. Since DTME08 / E04 is an IP address resolution machine, when editing communication instructions,
the address of its RS485 station number can be written to any value.
Example: If you want to use the Ethernet Modbus of DTME08 for communication function to read the
PV value of 8 channels, you can issue the command [FF 03 0268 0008]. The “FF” part can be modified
to any value. Only when using RS485 for communication, you need to confirm the station. The value
of the number selector (see section 2.4).
2.6.4 Troubleshooting
Fault conditions
cause of issue Troubleshooting method
found
DTME Not connected to the network
Please check if DTME is properly connected
to the network
Computer and DTME are in different
networks, blocked by network firewall
Please use the specified IP to find the
relevant settings
Cannot open
DTME settings
page
DTME Not connected to the network
Please check if DTME is properly connected
to the network
DCISoft communication setting error
Please check if the communication setting of
DCISoft is Ethernet
Computer and DTME are in different
networks, blocked by network firewall
Please use the specified IP to find the
relevant settings