Chapter 7:Appendix
DTM temperature controller operating manual
7-8
7.1.4 DTM-CT Series Accessory Operating Commands
When DTM-CT is combined with output status and alarm setting, there are the following distinctions
according to the value written in Hx262:
Set the content of address Hx262 to 0:
According to DTM host or measurement expansion module corresponding to the CT channel, when the
output is on, the CT alarm current value is measured; when the output is off, the CT alarm current value at
the previous turn-on is retained.
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
CT1 Alarm
current
Hx2C8 Hx2C9 Hx2CA Hx2CB Hx2CC Hx2CD Hx2CE Hx2CF
CT2 Alarm
current
Hx2D0 Hx2D1 Hx2D2 Hx2D3 Hx2D4 Hx2D5 Hx2D6 Hx2D7
Set the content of address Hx262 to 1:
According to DTM host or measurement expansion module corresponding to the CT1 channel, when the
output is on, measure the current value of CT1; when the output is off, measure the current value of CT1.
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
CT1 ON current Hx2C8 Hx2C9 Hx2CA Hx2CB Hx2CC Hx2CD Hx2CE Hx2CF
CT1 OFF current
Hx2D0 Hx2D1 Hx2D2 Hx2D3 Hx2D4 Hx2D5 Hx2D6 Hx2D7
Set the content of address Hx262 to 2:
According to DTM host or measurement expansion module corresponding to the CT1 channel, when the
output is on, the CT1 current value is measured; in addition, the full-time CT1 current value can be read.
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
CT1 ON current Hx2C8 Hx2C9 Hx2CA Hx2CB Hx2CC Hx2CD Hx2CE Hx2CF
CT1 Fulltime
current
Hx2D0 Hx2D1 Hx2D2 Hx2D3 Hx2D4 Hx2D5 Hx2D6 Hx2D7
DTM-CT series accessories are only used for current measurements; the address below can be used to
read the CT sensors current value (units: 0.1A), the y at the bottom represents the DTM -CT station number.
Please refer to [Section 6.3] for a detailed introduction.
Name
Description
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CT current
when OUT
being ON or
OFF
unit: 0.1A
range: 0 ~
9,999
Hy2C0 Hy2C1 Hy2C2 Hy2C3 Hy2C4 Hy2C5 Hy2C6 Hy2C7
Name
Address
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CT sensor
mode
0: 30A
1: 100A
Hy841 Bit0 Bit1 Bit2 Bit3 Bit4 Bit5 Bit6 Bit7
Notes:
1. x is the internal station number of the DTM host or measurement expansion module corresponding to
the CT.
2. y is the internal station number of DTM-CT030.