Chapter 2: Specifications and System Configuration
DTM temperature controller operating manual
2.6 Ethernet Communications Protocol Setting
DTME series models are Ethernet communication modules. IP addresses can be set through DCISoft (see
Chapter 7: Appendix for installation paths and usage methods for details). DTME series models
have the function of IP filtering. In addition, under the MDI / MDI-X automatic detection function, there is no
need to jumper when using the network line. The following will introduce the DTME series models in more
detail.
IP settings 192.168.1.5
Port setting: 502
2.6.1 Function
Automatically detect 10/100 Mbps transmission rate
MDI / MDI-X automatic detection
Support Modbus TCP communication protocol
Support EtherNet / IP Explicit message
Support EtherNet / IP I/O connection implicit message
Support software version: EIP Builder V1.07 or above
2.6.2 Functional Specifications
Interface
Items Specifications
Interface RJ-45 with Auto MDI/MDIX
Port number 1 Port
Transmission method IEEE802.3, IEEE802.3u
Cables Category 5e shielding 100M
Speed 10/100 Mbps Auto-Defect
Protocol
ICMP, IP, TCP, UDP, DHCP, BOOTP, Modbus
TCP, EtherNet/IP, Delta Configuration
Modbus TCP
Items Specifications
Normal Device type Server
Maximum number of
connections
4
Maximum data length for a
single connection
100 Words