Chapter 4: Output and Alarm Function Configuration
DTM temperature controller operating manual
4-6
ALM3 option Hx080 Hx081 Hx082 Hx083 Hx084 Hx085 Hx086 Hx087
ALM1 max. Hx980 Hx981 H982 Hx983 Hx984 Hx985 Hx986 Hx987
ALM1 min. Hx988 Hx989 Hx98A Hx98B Hx98C Hx98D Hx98E Hx98F
ALM2 max. Hx990 Hx991 Hx992 Hx993 Hx994 Hx995 Hx996 Hx997
ALM2 min. Hx998 Hx999 Hx99A Hx99B Hx99C Hx99D Hx99E Hx99F
ALM3 max. Hx9A0 Hx9A1 Hx9A2 Hx9A3 Hx9A4 Hx9A5 Hx9A6 Hx9A7
ALM3 min. Hx9A8 Hx9A9 Hx9AA Hx9AB Hx9AC Hx9AD Hx9AE Hx9AF
Table - Alarm function communications addresses
Note: x indicates internal station number.
F. Alarm STOP setting function: turn on/off the corresponding STOP alarm function according to the
Bit2 of Hx1E6. Bit2 content set to 0=disable, 1=enable
Table-Hx1E6 function setting communication content definition
Note: x indicates internal station number.
When the alarm activates, if the Bit2 setting function is enabled and the DTM state is switched to STOP,
the alarm will be turned off. On the contrary, if the Bit2 setting function is disabled and the DTM state is
switched to STOP, the alarm will keep on.
Hx1E6
Communication
Address
b7 b6 b5 b4 b3 b2 b1 b0
x x x x Auto multi-loop Alarm disable at STOP
Manual
multi-loop
Stop at
power ON