EasyManuals Logo

Delta DVP-PLC User Manual

Delta DVP-PLC
586 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #361 background imageLoading...
Page #361 background image
7 Application Instructions API 50-99
DVP-PLC APPLICATION MANUAL
7-77
CR #10 CR #9
Lower 16-bi
t
Designated CR number
Hi gher 16 -bit
d) Number of groups “n” to be transmitted: n = 2 in 16-bit instructions and n = 1 in 32-bit instructions mean
the same.
D0
D1
D2
D3
D4
D5
CR #5
CR #6
CR #7
CR #8
CR #9
CR #10
D0
D1
D2
D3
D4
D5
CR #5
CR #6
CR #7
CR #8
CR #9
CR #10
Designated device
Designated CR
Designated device
Designated CR
16-bit instruction when n=6
32-bit instruction when n=3
4. ES/EX/SS series MPU does not have M1083. During the execution of FROM/TO instruction, all external or
internal interruption subroutines will be forbidden. The interruptions are allowed only after FROM/TO instruction
finishes its execution. FROM/TO instruction can also be used in an interruption subroutine.
5. M1083 for switching instruction modes in SA/SX/SC/EH/EH2/SV series MPU:
a) When M1083 = Off, during the execution of FROM/TO instruction, all external or internal interruption
subroutines will be forbidden. The interruptions are allowed only after FROM/TO instruction finishes its
execution. FROM/TO instruction can also be used in an interruption subroutine.
b) When M1083 = On and an interruption signal occurs during the execution of FROM/TO instruction, the
interruption will be processed first (with a 100us delay) and the execution of FROM/TO will be stopped. After
the interruption subroutine finishes its execution, the program will jump to the next instructio of FROM/TO.
FROM/TO cannot be used in an interruption subroutine.
FROM/TO Application Example 1:
Adjust the A/D conversion curve of DVP-04AD. Set the OFFSET value of CH1 as 0V (= K0
LSB
) and GAIN value as
2.5V (= K2,000
LSB
).
M1002
TO K0 K1 H0 K1
TO K0 K33 H0 K1
X0
TO
K0 K18 K0 K1
TO
K0 K24 K2000 K1
1. Write H0 to CR#1 of anlog input module No. 0 and set CH1 as mode 0 (voltage input: -10V ~ +10V).
2. Write H0 to CR#33 and allow OFFSET/GAIN tuning in CH1 ~ CH4.
3. When X0 goes from Off to On, write the OFFSET value K0
LSB
into CR#18 and the GAIN value K2,000
LSB
into

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta DVP-PLC and is the answer not in the manual?

Delta DVP-PLC Specifications

General IconGeneral
ManufacturerDelta Electronics
ModelDVP-PLC
CategoryController
Humidity5% to 95% RH, non-condensing
Programming LanguageLadder Diagram (LD), Instruction List (IL), Sequential Function Chart (SFC)
CPU TypeVarious, depending on the specific model within the DVP series (e.g., ES2, EX2, SX2, SA2, EH3, etc.)
Operating TemperatureTypically 0°C to 55°C (32°F to 131°F)
Storage TemperatureTypically -25°C to 70°C (-13°F to 158°F)

Related product manuals