8 Application Instructions API 100-149
DVP-PLC Application Manual
8-21
The operation of CRC checksum:
Step 1: Make the 16-bit register (CRC register) = FFFFH
Step 2: Exclusive OR the first 8-bit byte message instruction and the low-bit 16-bit CRC register. Store the
result in CRC register.
Step 3: Shift the CRC register one bit to the right and fill 0 in the higher bit.
Step 4: Check the value that shifts to the right. If it is 0, store the new value from Step 3 into the CRC register,
otherwise, Exclusive OR A001H and the CRC register, and store the result in the CRC register.
Step 5: Repeat Step 3 ~ 4 and finish calculating the 8 bits.
Step 6: Repeat Steps 2 ~ 5 for obtaining the next 8-bit message instruction until all the message instructions
are calculated. In the end, the obtained CRC register value is the CRC checksum. Be aware that
CRC checksum should be placed in the checksum of the message instruction.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta DVP-PLC and is the answer not in the manual?

Delta DVP-PLC Specifications

General IconGeneral
ManufacturerDelta Electronics
ModelDVP-PLC
CategoryController
Humidity5% to 95% RH, non-condensing
Programming LanguageLadder Diagram (LD), Instruction List (IL), Sequential Function Chart (SFC)
CPU TypeVarious, depending on the specific model within the DVP series (e.g., ES2, EX2, SX2, SA2, EH3, etc.)
Operating TemperatureTypically 0°C to 55°C (32°F to 131°F)
Storage TemperatureTypically -25°C to 70°C (-13°F to 158°F)

Related product manuals