9 Application Instructions API 150-199
DVP-PLC Application Manual
9-6
Registers for received data (responding messages)
Register DATA Explanation
D1070 Low ‘0’ 30 H ADR 1
D1070 High ‘1’ 31 H ADR 0
D1071 Low ‘0’ 30 H CMD 1
D1071 High ‘6’ 36 H CMD 0
D1072 Low ‘0’ 30 H
D1072 High ‘1’ 31 H
D1073 Low ‘0’ 30 H
D1073 High ‘0’ 30 H
Data Address
D1074 Low ‘1’ 31 H
D1074 High ‘7’ 37 H
D1075 Low ‘7’ 37 H
D1075 High ‘0’ 30 H
Data content
D1076 Low ‘7’ 37 H LRC CHK 1
D1076 High ‘1’ 31 H LRC CHK 0
9. RTU Mode: When PLC is connected to VFD-S AC motor drive
PLC Ö VFD-S, PLC sends: “01 06 2000 0012 02 07”
VFD-S Ö PLC, PLC receives: “01 06 2000 0012 02 07”
Registers for sent data (sending message)
Register DATA Explanation
D1256 Low 01 H Address
D1257 Low 06 H Function
D1258 Low 20 H
D1259 Low 00 H
Data Address
D1260 Low 00 H
D1261 Low 12 H
Data content The content of register D50 (H12)
D1262 Low 02 H CRC CHK Low
D1263 Low 07 H CRC CHK High
Registers for received data (responding message)
Register DATA Explanation
D1070 Low 01 H Address
D1071 Low 06 H Function
D1072 Low 20 H
D1073 Low 00 H
Data Address
D1074 Low 00 H
D1075 Low 12 H
Data content
D1076 Low 02 H CRC CHK Low
D1077 Low 07 H CRC CHK High
Program Example 3:
1. Function code K16(H10): For writing many word data into register.
When PLC is connected to VFD-S AC motor drive: M1143 = Off, in ASCII mode
When PLC is connected to VFD-S AC motor drive: M1143 = On, in RTU mode
2. When in ASCII mode, the user stores the data to be written in the designated register D50 in hex format. The
data sent back from AC motor drive are stored in D1070 ~ D1076.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta DVP-PLC and is the answer not in the manual?

Delta DVP-PLC Specifications

General IconGeneral
ManufacturerDelta Electronics
ModelDVP-PLC
CategoryController
Humidity5% to 95% RH, non-condensing
Programming LanguageLadder Diagram (LD), Instruction List (IL), Sequential Function Chart (SFC)
CPU TypeVarious, depending on the specific model within the DVP series (e.g., ES2, EX2, SX2, SA2, EH3, etc.)
Operating TemperatureTypically 0°C to 55°C (32°F to 131°F)
Storage TemperatureTypically -25°C to 70°C (-13°F to 158°F)