14 High Speed Compare and Capture
DVP-PM Application Manual
14-9
Capture initial setting: apply 1 set of Capture (n=0). FROM/TO 6 pieces of data.
Capture setting:
n=0, Source: C204(b[3:0]=4); Enable Capture function(b[5:4]=0); Trigger switch of Capture function:
X_DOG(b[15:12]=5.
M1002
MOV
K0
D0
MOV
MOV
M1
M2
TO
K253
K1
RST
M2
K0
D1
K6
D20
MOV K6
D60
MOV
H5004
D2
MOV
K100
D4
RST
M1
RST
D0
D20
M3
FROM
K253
K1
RST
M3
D40
D60
M4
MOV
K1
K1M1204
SET
M5
RST
M4
M5
DCNT
C204
K10
Sequential control process:
Step 1: Initial setting for Capture function when O100 is activated to set ON M1002:
(1) D0 = 0 Æ Specify the number of the starting set. n = 0 indicates the first set.
(2) D1 = 0
(3) D20 = 6 Æ Set up data length for TO instruction: 6 words, 1 set of data for Capture function
(4) D60 = 6 Æ Set up data length for FROM instruction: 6 words, 1 set of data for Capture function.
Step 2: Set M1. Specify the data for Capture function in control registers and data registers.