eZV-440 Application Guide
Edition 2.6
Page 31 of 84
3. If you had selected the SpaceTempSetpoint_ option to set up a resistive slider, in additional
settings, in the SetpointSliderMinResistance field, enter the minimum resistance of the
setpoint slider. In the SetpointSliderMaxResistance field, enter the maximum resistance
of the setpoint slider.
To enter the occupancy setpoint offset range for this resistive slider, go to the Setpoints tab
and enter the ± offset in the OccSetpointOffsetRange field.
4. (enteliWEB only) The Input Name field displays the object's name. You can change this
name by clearing the field and entering a new name.
For a list of input configuration software objects that correspond to each function, see the Input
Configuration Objects topic.
Setting Up an Airflow Sensor
Introduction
This topic describes how to set up an airflow pressure sensor on the eZV-440 controller on the
Local Inputs tab.
On the eZV-440 controller, physical input 6 is reserved for the onboard differential pressure sensor.
Set Up an Airflow Sensor
On the Local Inputs tab, next to input number 6, select VAVAirflow_ in the Function field.
(enteliWEB only) The Input Name field displays the object's name. You can change this name by
clearing the field and entering a new name.
Setting Up Damper Feedback
This topic describes how to set up damper position feedback using the Local Inputs tab on the
configuration page. The actuator must have a position feedback feature.
On the eZV-440 controller, the damper feedback signals should be configured on the controller
input 5.
Set Up Damper Feedback
1. Wire the actuator to the controller's physical input.
2. Next to the input number that you've assigned to the actuator, in the Function field, select
Damper1Feedback_. With the eZV-440 controller, you would use input number 5.