LINKnet I/O Tab
Page 48 of 84 eZV-440 Application Guide
Edition 2.6
Set Up the Button Elements
On the LINKnet I/O tab, in the Button Options section, next to the button you want to program,
select one of the following functions that you want to assign to that button:
Function
Recommended
corresponding
DNS-24L button
Select this option if you want to:
NotUsed_ Not applicable Designate custom button behavior using GCL or
if you want a blank button.
OccupancyOff_ Button 1
Turns on the standby occupancy mode.
In the additional settings, in the
PushButtonOvrdTime field, you can enter how
long the button override should last.
OccupancyOn_ Button 2
Turns on the occupied mode.
In the additional settings, in the
PushButtonOvrdTime field, you can enter how
long the button override should last.
OccupancyToggle_ Button 1 (DNS
Fan model)
Toggle between standby and occupied modes
during scheduled occupancy periods.
When pushed during unoccupied mode it starts
an occupancy override timer. When an override
has been activated, pushing the button again will
cancel the override and reset the override timer
back to zero.
In the additional settings, in the
PushButtonOvrdTime field, you can enter how
long the button override should last.
TempUnitsToggle_ Not applicable
Recommended for use with the eZNS network
sensor. Toggles between displaying the
temperature in Celsius and the temperature in
Fahrenheit.