enteliZONE Database Configuration Objects
Page 74 of 84 eZV-440 Application Guide
Edition 2.6
Output Configuration Objects
Object Name
Object
Ref
Default Description
TimePropClgMin AV150 0%
The minimum cooling output value. The time-
proportional algorithm scales the cooling output
using this minimum value.
TimePropClgMax AV151 100%
The maximum cooling output value. The time-
proportional algorithm scales the cooling output
using this maximum value.
TimePropHtgMin AV152 0%
The minimum heating output value. The time-
proportional algorithm scales the heating output
using this minimum value.
TimePropHtgMax AV153 100%
The maximum heating output value. The time-
proportional algorithm scales the heating output
using this maximum value.
TimePropPeriod AV154 100s
The period of the pulse that is used to modulate
the time-proportional heating and cooling outputs.
Heat1FanMin AV199 0
The optional fan speed interlock when duct Heat 1
stage is running.
Heat2FanMin AV200 0
The optional fan speed interlock when duct Heat 2
stage is running.
Heat3FanMin AV201 0
The optional fan speed interlock when duct Heat 3
stage is running.
Cool1FanMin AV202 0
The optional fan speed interlock when duct Cool 1
stage is running.
Cool2FanMin AV203 0
The optional fan speed interlock when duct Cool 2
stage is running.
HeatCoolLoad AV802 0 %
Monitors if the system is in heating or cooling
mode (<0 = cooling, >0 = heating).
Heat1 AV803 100 % First heating stage.
Heat2 AV804 0 % Second heating stage.
Heat3 AV805 0 % Third heating stage.
Cool1 AV806 0 % First cooling stage.
Cool2 AV807 0 % Second cooling stage.
AirflowDemand AV808 100 % VAV airflow demand.
Fan1 AV810 0 % First fan stage.