eZV-440 Application Guide
Edition 2.6
Page 75 of 84
Object Name
Object
Ref
Default Description
Fan2 AV811 0 % Second fan stage.
Fan3 AV812 0 % Third fan stage.
DemandCtrlVent AV813 0 %
Demand Control Ventilation. Its value reflects the
CO2 demand (VAV/VVT).
Custom1* AV815 0 %
Custom stage associated with GCL controlled
output.
Custom2* AV816 0 %
Custom stage associated with GCL controlled
output.
DamperCmd AV832 0 %
Sets the damper position for the
VentilationDamper output (VAV/VVT).
Airflow Status BV800 Off_
Used to display the status of airflow in the duct
(VAV/VVT).
* Available only with enteliZONE programmable models.
Setpoint Configuration Objects
Object Name
Object
Ref
Default Description
OccHeating Setpoint AV100 21
Celsius
Base heating setpoint in occupied mode
OccCooling Setpoint AV101 24
Celsius
Base cooling setpoint in occupied mode
UnOccHeating Set-
point
AV102 17
Celsius
Unoccupied heating setpoint
UnOccCooling Set-
point
AV103 21
Celsius
Unoccupied cooling setpoint
HeatCool
ChangeoverDelay
AV104 5
minutes
Time delay between heating and cooling to
prevent overshoot when the heating and
cooling setpoints are close together. Range
between 1 to 30 minutes.
Standby Setback AV105 1 Celsius
Extra setpoint offset added in standby mode.