enteliZONE Database Configuration Objects
Page 76 of 84 eZV-440 Application Guide
Edition 2.6
Object Name
Object
Ref
Default Description
EcoMode Setback AV106 1 Celsius
Amount of setback that gets subtracted from
heating and added the cooling setpoints
when controller is in eco mode.
OccSetpoint Off-
setRange
AV107 3 Celsius
Determines the offset range available to
change the Occupied Heating and Cooling
setpoints at a LINKnet stat interface or a
hardwired setpoint adjust input.
CoolingMinimum AV124
0 CFM
(VAV)
0%
(VVT)
Minimum cooling airflow setpoint (VAV)
Damper position at this setpoint (VVT)
Cooling Maximum AV125
0 CFM
(VAV)
0%
(VVT)
Maximum cooling airflow setpoint (VAV)
Damper position at this setpoint (VVT)
Heating Minimum AV126
0 CFM
(VAV)
0%
(VVT)
Minimum heating airflow setpoint (VAV)
Damper position at this setpoint (VVT)
Heating Maximum AV127
0 CFM
(VAV)
0%
(VVT)
Maximum heating airflow setpoint (VAV)
Damper position at this setpoint (VVT)
Standby Minimum AV129 Cooling
Minimum
Minimum airflow setpoint in standby mode
where there is no heating or cooling load
(VAV Damper position at this setpoint (VVT)
Airflow Fail-
ureSetpoint
AV130 80%
Cooling
Minimum
Airflow failure setpoint (VAV) Damper
position at this setpoint (VVT)
ParallelFan FlowSet-
point
AV131 Heating
Minimum
The parallel fans turn on if airflow falls below
this setpoint to maintain adequate air mixing.
OATHeat Lock-
outSetpoint
AV160 99
Celsius
Outside air temperature heat lockout setpoint.