Chapter 11 Summary of Parameter SettingsME300
11-7
Pr. Explanation Settings Default
00-30
Master frequency
command source
(HAND, LOCAL)
0: Digital keypad
1: RS-485 communication input
2: External analog input (refer to Pr.03-00)
3: External UP / DOWN terminal
(multi-function input terminals)
7: Digital keypad potentiometer knob
9: PID controller
Note:
HOA (Hand-Off-Auto) function is valid only when you use with
MO function setting 41 and 56 or with KPC-CC01 (optional).
0
00-31
Operation command
source (HAND, LOCAL)
0: Digital keypad
1: External terminal
2: RS-485 communication input
Note:
HOA (Hand-Off-Auto) function is valid only when you use with
MO function setting 41 and 56 or with KPC-CC01 (optional).
0
00-32
Digital keypad STOP
function
0: STOP key disabled
1: STOP key enabled
0
00-33 RPWM Mode Selection
0: Disabled
1: RPWM mode 1
2: RPWM mode 2
3: RPWM mode 3
0
00-34 RPWM Range
0.0–4.0 kHz
Pr.00-17 = 4 kHz, 8 kHz: the setting range is 0.0–2.0 kHz
Pr.00-17 = 5–7 kHz: the setting range is 0.0–4.0 kHz
0.0
00-35
Auxiliary frequency
source
0: Master and auxiliary frequency function disabled
1: Digital keypad
2: RS-485 communication input
3: Analog input
4: External UP / DOWN key input
(multi-function input terminals)
7: Digital keypad potentiometer knob
0
00-36
Master and auxiliary
frequency command
selection
0: Master + auxiliary frequency
1: Master – auxiliary frequency
2: Auxiliary – master frequency
0
00-48 Display filter time (current) 0.001–65.535 sec. 0.100
00-49
Display filter time
(keypad)
0.001–65.535 sec. 0.100
00-50 Software version (date) Read only Read only