Chapter 12 Description of Parameter Settings
ME300
12.1-14-1
14 Protection Parameters (2)
You can set this parameter during operation.
14-50
Output Frequency at Malfunction 2
14-54
Output Frequency at Malfunction 3
14-58
Output Frequency at Malfunction 4
14-62
Output Frequency at Malfunction 5
14-66
Output Frequency at Malfunction 6
Default:
Read only
Settings 0.00599.00 Hz
When an error occurs, you can check the output frequency for the malfunction. If the error
happens again, this parameter overwrites the previous record.
14-51
DC bus Voltage at Malfunction 2
14-55
DC bus Voltage at Malfunction 3
14-59
DC bus Voltage at Malfunction 4
14-63
DC bus Voltage at Malfunction 5
14-67
DC bus Voltage at Malfunction 6
Default:
Read only
Settings 0.06553.5 V
When an error occurs, you can check the DC voltage for the malfunction. If the error happens
again, this parameter overwrites the previous record.
14-52
Output Current at Malfunction 2
14-56
Output Current at Malfunction 3
14-60
Output Current at Malfunction 4
14-64
Output Current at Malfunction 5
14-68
Output Current at Malfunction 6
Default:
Read only
Settings 0.00655.35 Amp
When an error occurs, you can check the output current for the malfunction. If the error happens
again, this parameter overwrites the previous record.
14-53
IGBT Temperature at Malfunction 2
14-57
IGBT Temperature at Malfunction 3
14-61
IGBT Temperature at Malfunction 4
14-65
IGBT Temperature at Malfunction 5
14-69
IGBT Temperature at Malfunction 6
Default: Read only
Settings -3276.73276.7
o
C
When an error occurs, you can check the IGBT temperature for the malfunction. If the error
happens again, this parameter overwrites the previous record.