Chapter 7 Optional AccessoriesME300
7-55
7-13 Digital KeypadKPC-CC01, KPC-CE01
7-13-1 Keypad Panel introduction
The default communication protocol for ME300 is ASCII 9600, 7, N, 2, whereas the default
communication protocol for KPC-CC01 is RTU 19200, 8, N, 2. So you must set the ME300
communication parameters as follows to connect it to KPC-CC01.
Pr.09-00 Communication Address: Settings = 1
Pr.09-01 COM1 Transmission Speed (Baud rate): Settings = 19.2 Kbps
Pr.09-04 COM1 Communication Protocol: Settings = 13: 8N2 (RTU)
KPC-CC01
KPC-CE01
Communication Interface
RJ45 (socket),
RS-485 interface
Communication Protocol
RTU19200, 8, N, 2
Installation Method
Install the embedded type on the surface of the
control box. The front cover is waterproof.
Buy a MKC-KPPK model for wall mounting or
embedded mounting. Its protection level is IP66.
The maximum RJ45 extension lead is 5 m (16 ft)
T
his keypad can only be used on Deltas motor
drive C2000, CH2000, CP2000, MS300, MH300,
and ME300.
Keypad Functions Description
Key
Descriptions
S
tart Operation Key
1. Only valid when the source of operation command is the keypad.
2. Operates the AC motor drive by the function setting. The RUN LED will be ON.
3. Can be pressed repeatedly at the stop process.
S
top Command Key.
1. This key has the highest priority when the command is from the keypad.
2. When it receives the STOP command, regardless of whether the AC motor drive is i
n
oper
ation or stop status, the AC motor drive executes the STOPcommand.
3. Use the RESET key to reset the drive after a fault occurs.
4. If you cannot reset after the error:
a. The condition which triggers the fault is not cleared. After you clear the condition, yo
u
c
an then reset the fault.
b. The drive is in fault status when powered on. After you clear the condition, restart
and
then you can reset the fault.
Operation Direction Key
1.
Only controls the operation direction, NOT the drive activation. FWD: forward, REV: reverse.
2. Refer to LED Descriptions for more details.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ME300 Series and is the answer not in the manual?

Delta ME300 Series Specifications

General IconGeneral
Power Rating0.4 kW ~ 110 kW
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
CommunicationRS-485
Storage Temperature-20-60°C
DimensionsVaries by model
WeightVaries by model
Input Voltage3-phase 220VAC
Humidity90% RH, non-condensing