EasyManua.ls Logo

Delta ME300 Series - Page 265

Delta ME300 Series
457 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter SettingsME300
12.1-03-14
03-15
Analog Input Filter Time (AVI)
03-16
Analog Input Filter Time (ACI)
Default: 0.01
Settings
0.0020.00 sec.
Use these input delays to filter a noisy analog signal.
When the time constant setting is too large, the control is stable but the control response is
slow. When the time constant setting is too small, the control response is faster but the control
may be unstable. For optimal setting, adjust the setting based on the control stability or the
control response.
03-19
Signal Loss Selection for the Analog Input 4–20 mA
Default: 0
Settings 0: Disable
1: Continue operation at the last frequency
2: Decelerate to 0 Hz
3: Stop immediately and display ACE
Determines the treatment when the 4–20 mA signal is lost, when ACIc (Pr.03-28 = 0).
When Pr.03-28 2, the voltage input to AVI terminal is 010 V or 020 mA, and Pr.03-19 is invalid.
When the setting is 1 or 2, the keypad displays the warning code ANL”. It keeps blinking until the
ACI signal is recovered.
When the motor drive stops, the warning condition does not continue to exist, so the warning
disappears.
03-20
AFM Analog Output Selection
Default: 0
Settings
0–23
Function Chart
Settings
Functions Descriptions
0 Output frequency (Hz) Maximum frequency Pr.01-00 is processed as 100%.
1 Frequency command (Hz) Maximum frequency Pr.01-00 is processed as 100%.
2 Motor speed (Hz) Maximum frequency Pr.01-00 is processed as 100%.
3 Output current (rms) (2.5 × rated current) is processed as 100%.
4 Output voltage (2 × rated voltage) is processed as 100%.
5 DC bus voltage 450 V (900 V) = 100%
6 Power factor -1.0001.000 = 100%
7 Power (2 × rated power) is processed as 100%.
9 AVI 0–10 V = 0100%
12 Iq current command (2.5 × rated current) is processed as 100%.
13 Iq feedback value (2.5 × rated current) is processed as 100%.
14 Id current command (2.5 × rated current) is processed as 100%.
15 Id feedback value (2.5 × rated current) is processed as 100%.
16 Vq-axis voltage command 250 V (500 V) = 100%

Table of Contents