Chapter 12 Description of Parameter Settings
ME300
12.1-06-5
06-05
Accel./Decel. Time Selection for Stall Prevention at Constant Speed
Default: 0
Settings
0: By current acceleration / deceleration time
1: By the first acceleration / deceleration time
2: By the second acceleration / deceleration time
3: By the third acceleration / deceleration time
4: By the fourth acceleration / deceleration time
5: By Auto-acceleration / auto-deceleration
Sets the acceleration / deceleration time selection when stall prevention occurs at constant speed.
06-06
Over-torque Detection Selection (Motor 1)
Default: 0
Settings
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
06-09
Over-torque Detection Selection (Motor 2)
Default: 0
Settings
0: No function
1: Continue operation after over
-torque detection during constant speed
operation
2: Stop after over
-torque detection during constant speed operation
3: Continue operation after over
-torque detection during RUN
4: Stop after over
-torque detection during RUN
When you set Pr.06-06 and Pr.06-09 to 1 or 3, a warning message displays but there is no error
record.
When you set Pr.06-06 and Pr.06-09 to 2 or 4, a warning message displays and there is an error
record.