Chapter 12 Description of Parameter SettingsME300
12.1-07-4
07-09
Current Limit of Speed Tracking
Default: 100
Settings 20200%
The AC motor drive executes speed tracking only if the output current is greater than the value
set in Pr.07-09.
The maximum current for speed tracking affects the synchronous time. The larger the parameter
setting is, the faster the synchronization occurs. However, if the parameter setting is too large, the
overload protection function may be activated.
Time
B.B. Speed tracking: from minimum output frequency
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time Pr. 07-08
Speed tracking
Synchronous speed detectio
Output frequency (H)
Output voltage (V)
Output current
Pr. 07-09
Current level of
speed tracking
FWD Run
B.B.
A
B.B.
A
Time
Over-current stall prevention
Output frequency (H)
Output voltage (V)
Output current
Pr. 06-03
Over-current stall
prevention level
during accel.
FWD Run
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time Pr. 07-08
Speed tracking
Synchronous speed detection

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ME300 Series and is the answer not in the manual?

Delta ME300 Series Specifications

General IconGeneral
Power Rating0.4 kW ~ 110 kW
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
CommunicationRS-485
Storage Temperature-20-60°C
DimensionsVaries by model
WeightVaries by model
Input Voltage3-phase 220VAC
Humidity90% RH, non-condensing

Related product manuals