Chapter 12 Description of Parameter SettingsME300
12.1-07-13
ratio is slower than expected, increase the parameter setting value; otherwise, decrease the
setting value.
07-29
Slip Deviation Level
Default: 0
Settings 0.0100.0%
0: No detection
07-30
Slip Deviation Detection Time
Default: 1.0
Settings 0.010.0 sec.
07-31
Slip Deviation Action
Default: 0
Settings 0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
Parameters Pr.07-29Pr.07-31 set the allowable slip level / time and the over-slip action when the
drive is running.
07-32
Motor Shock Compensation Factor
Default: 1000
Settings
0–10000
If there are current wave motions in the motor in some specific area, setting this parameter can
effectively improve this situation.
When the current wave motion occurs in low frequency and high-power, increase the value for
Pr.07-32.
07-33
Auto-restart Interval of Fault
Default: 60.0
Settings 0.06000.0 sec.
When a reset/restart occurs after a fault, the drive uses Pr.07-33 as a timer and starts counting
the number of faults within this time period. Within this period, if the number of faults does not
exceed the setting for Pr.07-11, the counting clears and starts from 0 when the next fault occurs.
07-38
PMSVC Voltage Feed Forward Gain
Default: 1.00
Settings 0.502.00
Adjusts the PMSVC voltage feedback forward gain, and to meet the demand of rapid feedback
application.
Pr.07-38 = 1.00 means forward feedback = Ke × motor rotor speed
Refer to Section 12-2 “PMSVC adjustmentfor details.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ME300 Series and is the answer not in the manual?

Delta ME300 Series Specifications

General IconGeneral
Power Rating0.4 kW ~ 110 kW
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
CommunicationRS-485
Storage Temperature-20-60°C
DimensionsVaries by model
WeightVaries by model
Input Voltage3-phase 220VAC
Humidity90% RH, non-condensing

Related product manuals