EasyManua.ls Logo

Delta ME300 Series - Page 319

Delta ME300 Series
457 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter Settings
ME300
12.1-08-4
08-04
Upper Limit of Integral Control
Default: 100.0
Settings 0.0100.0%
Defines an upper bound for the integral gain (I) and therefore limits the master frequency. The
formula is:
Integral upper bound = Maximum Operation Frequency (Pr.01-00) x (Pr.08-04%). An excessive
integral value causes a slow response due to sudden load changes and may cause motor stall or
machine damage.
08-05
PID Output Command Limit (Positive Limit)
Default: 100.0
Settings 0.0100.0%
Defines the percentage of the output frequency limit during the PID control. The formula is Output
Frequency Limit = Maximum Operation Frequency (Pr.01-00) × Pr.08-05%.
08-06
PID Feedback Value by Communication Protocol
Default: 0.00
Settings
-200.00
200.00%
Use communication to set the PID feedback value when the PID feedback input is set to
communication (Pr.08-00 = 7 or 8).
08-07
PID Delay Time
Default: 0.0
Settings 0.02.5 sec.
08-20
PID Mode Selection
Default: 0
Settings
0: Serial connection
1: Parallel connection
0: Use conventional PID control structure.
1: The proportional gain, integral gain and differential gain are independent. You can customize
the P, I and D value to fit your application.
Pr.08-07 determines the primary low pass filter time when in PID control. Setting a large time
constant may slow down the drive’s response rate.
PID control output frequency is filtered with a primary low pass function. This function can filter a
mix of frequencies. A long primary low pass time means the filter degree is high and a short
primary low pass time means the filter degree is low.
Inappropriate delay time setting may cause system error.
PI Control:
Controlled only by the P action, so the deviation cannot be entirely eliminated. In general, to
eliminate residual deviations, use the P + I controls. When you use the PI control, it eliminates the
deviation caused by the targeted value changes and the constant external interferences. However,
if the I action is too powerful, it delays the response when there is rapid variation. You can use the
P action by itself to control the loading system with the integral components.

Table of Contents

Related product manuals