Chapter 12 Description of Parameter Settings
ME300
12.1-08-6
08-08
Feedback Signal Detection Time
Default: 0.0
Settings 0.03600.0 sec.
Pr.08-08 is valid only for Pr.03-28 = 2 (420 mA).
This parameter sets the detection time for abnormal PID signal feedback. Setting the detection
time to 0.0 disables the detection function.
08-09
Feedback Signal Fault Treatment
Default: 0
Settings 0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: Warn and operate at last frequency
This parameter is valid only for Pr.03-28 = 2 (4–20 mA)..
The AC motor drive acts when the analog PID feedback is abnormal.
08-10
Sleep Level
Default: 0.00
Settings 0.00599.00 Hz / 0.00~200.00%
Determines the sleep frequency, and if the sleep time and the wake-up frequency are enabled
or disabled.
Pr.08-10 = 0: Disabled
Pr.08-10 = 0: Enabled
08-11
Wake-up Level
Default: 0.00
Settings 0.00599.00 Hz / 0.00~200.00%
Sleep and wake-up function are started up according to the setting of Pr.08-10.
Pr.08-10 = 0, not start up; Pr.08-10 0, start up.
When Pr.08-18 = 0, the unit for Pr.08-10 and that for Pr.08-11 switch to frequency. The settings
are between 0.00599.00 Hz.
When Pr.08-18 = 1, the unit for Pr.08-10 and that for Pr.08-11 switch to percentage. The settings
then are between 0.00200.00%.The percentage is based on the current command value, not the
maximum value. For example, if the maximum value is 100 kg, and the current value is 30 kg,
then if Pr.08-11 = 40%, the value is 12 kg.
08-12
Sleep Delay Time
Default: 0.0
Settings 0.06000.0 sec.
When the Frequency command is smaller than the sleep frequency and less than the sleep time,
the Frequency command is equal to the sleep frequency. However, the Frequency command
remains at 0.00 Hz until the Frequency command becomes equal to or larger than the wake-up
frequency.