EasyManua.ls Logo

Delta ME300 Series - Page 328

Delta ME300 Series
457 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter Settings
ME300
12.1-08-13
When Pr.08-65 = 0, PID controller architecture diagram as shown below:
When Pr.08-65 0, PID controller architecture diagram as shown below:
When Pr.08-65 is not set to 0, Pr.00-20 is automatically set to 9.
When Pr.08-65 is set to 1, PID command can be setting by Pr.08-66; when Pr.08-65 is not set to
1, PID command is displayed from Pr.08-66.
If Pr.08-65 selects 2, 4, and 6, the corresponding communication address is C2003H.
08-66
PID target value setting
Default: 50.00
Settings -100.00100.00%
The target value setting of PID controller (Pr.08-66) is a relative value
08-67
Master and auxiliary reverse running cutoff frequency
Default: 10.0
Settings 0.0100.0%
100% corresponds to Pr.01-00 the Maximum operation frequency
In some cases, it is only possible for the PID to control the value setting and the feedback in the
same situation when the PID output frequency is negative (the motor is reversed). However, an
excessively high reversal frequency is not allowed in some cases, and Pr.08-67 is used to
determine the upper limit of the reversal frequency

Table of Contents

Related product manuals