Chapter 12 Description of Parameter Settings
ME300
12.1-10-3
10-52
Injection Magnitude
Default: 15.0 / 30.0
Settings 115V / 230V series: 100.0 V
460V series: 200.0 V
Note: The setting range varies depending on the voltage.
The parameter is the magnitude command for the high frequency injection signal in PM SVC
control mode.
Increasing the parameter can increase the accuracy of the angle estimation, but the
electromagnetic noise might be louder if the setting value is too high.
The system uses this parameter when the motors parameter is Auto”. This parameter
influences the angle estimation accuracy.
When the ratio of the salient pole (Lq/Ld) is lower, increase Pr.10-52 to make the angle detection
more accurate.
Pr.10-52 is valid only when Pr.10-53 = 2.
10-53
Angle detection method
Default: 0
Settings 0: Disabled
1: Force attracting the rotor to zero degrees
2: High frequency injection
3: Pulse injection
Set to 2 for IPM; set to 3 for SPM. If these settings cause problems, then set the parameter to 1.