Chapter 14 Fault Codes and Descriptions
ME300
14-36
No. Display on LED Keypad Fault Name Fault Descriptions
63
Over-slip
(oSL)
The slip is abnormal. By using the maximum slip
(Pr.10-29) as the base, when the drive outputs at
constant speed, and the F > H or F < H exceeds
Pr.07-29 level and Pr.07-30 setting time, oSL occurs.
oSL occurs only when using a general induction motor.
Action and Reset
Action condition
Pr.07-29 (100% of Pr.07-29Pr.10-29 Top limit of frequency deviation)
Action time Pr.07-30
Fault treatment parameter
Pr.07-31
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
Reset method
Auto
When Pr.07-310, oSL is a “Warming
When the drive outputs at constant speed, and the F > H or F <
H no
longer exceeds the Pr.07-29 level, the oSL warning is
automatically
cleared.
Manual
When Pr.07-311 or 2, oSL is a Fault”. You must reset manually.
Reset condition Immediately reset
Record
When Pr.07-311 or 2, oSL is a Fault, and the fault is recorded.
Cause Corrective Actions
Check if the motor setting is
correct.
Check the motor parameter.
The load is too large. Decrease the load.
Check if the settings for Pr.07-29,
Pr.07-30 and Pr.10-29
are properly
set.
Check the parameter settings for oSL protection.