Chapter 14 Fault Codes and Descriptions
ME300 
 
  No.  Display on LED Keypad  Fault Name  Fault Descriptions 
63 
 
Over-slip 
(oSL) 
The slip is abnormal. By using the maximum slip 
(Pr.10-29) as the base, when the drive outputs at 
constant speed, and the F > H or F < H exceeds   
Pr.07-29 level and Pr.07-30 setting time, oSL occurs. 
oSL occurs only when using a general induction motor. 
Action and Reset 
Action condition 
Pr.07-29 (100% of Pr.07-29=Pr.10-29 Top limit of frequency deviation) 
Action time  Pr.07-30 
Fault treatment parameter 
Pr.07-31 
0: Warn and continue operation 
1: Fault and ramp to stop 
2: Fault and coast to stop 
3: No warning 
Reset method 
Auto 
When Pr.07-31=0, oSL is a “Warming” 
When the drive outputs at constant speed, and the F > H or F < 
longer exceeds the  Pr.07-29  level, the oSL warning is 
cleared. 
Manual 
When Pr.07-31=1 or 2, oSL is a “Fault”. You must reset manually. 
Reset condition  Immediately reset 
Record 
When Pr.07-31=1 or 2, oSL is a “Fault”, and the fault is recorded. 
Cause  Corrective Actions 
Check if the motor setting is 
correct. 
Check the motor parameter. 
The load is too large.  Decrease the load. 
Check if the settings for Pr.07-29, 
Pr.07-30 and Pr.10-29 
set. 
Check the parameter settings for oSL protection.