4. Description of Parameters
4-7
Parameter
code
Function of the parameter Settings
Default
value
VF
FOCPG
FOCPM
01-12
No-load current of the
induction motor (A)
0~Default value of Parameter 01-08 #.## ○
01-13
Stator resistance (Rs) of the
induction Motor
0~65.535Ω
#.### ○
01-14
Rotor resistance (Rr) of the
induction Motor
0~65.535Ω
#.### ○
01-15
Magnetizing inductance (Lm)
of the induction Motor
0.0~6553.5mH #.# ○
01-16
Total leakage inductance (Lx)
of the induction motor
0.0~6553.5mH #.# ○
01-17
Rated current of the
synchronous motor
0~655.35 Amps 0.00 ○
01-18
Rated power of the
synchronous motor
0.00 – 655.35kW 0.00 ○
01-19
Rated speed of the
synchronous motor
0~65535rpm 0 ○
01-20
Number of poles of the
synchronous motor
2~20 6 ○
01-21
Inertia of the synchronous
motor’s rotor
0.0~6553.5 *10
-4
kg.m
2
0.0 ○
01-22
Stator’s phase resistance
(Rs) of the synchronous
motor
0.000~65.535Ω
0.000 ○
01-23
Stator’s phase inductance
(Ld) of the synchronous
motor
0.00.0~655.35mH 0.00 ○
01-24
Stator’s phase inductance
(Lq) of the synchronous
motor
0.00.0~655.35mH 0.00 ○
01-25
Back EMF of the
synchronous motor
0~65535 V/krpm 0 ○
01-26 Encode type
0: ABZ
1: ABZ+HALL (only used for Delta’s servo motors)
2: ABZ+HALL
3: Resolver
3 ○
01-27
PG Offset angle of
synchronous motor
0.0~360.0° 0.0 ○